Product description of safety module CAMC-G-S3
2.12
Runtime performance
2.12.1
Sampling times
The safety module records the input and output variables at regular intervals.
The variables are recorded at two fixed cycle rates è Tab. 2.90.
Cycle
Sampling
frequency
TSample
typ. 8 KHz
TLogic
500 Hz
Tab. 2.90 Sampling times of the safety module
This means that the recording of the input signals can be affected by a maximum jitter of
T
+ T
Logic
Sample
after 2.125 ms. The start of a safety function can also be affected by this jitter, relative to
the input signal. The jitter is taken into account in the specified reaction times of the indi
vidual function blocks.
2.12.2
Reaction time on request of a safety function
The reaction time is made up of three components (Fig. 2.38):
LIN_x
DIN40A/B
INPUT
FILTER
LIN_D40
+
LOGIC
T
I
Fig. 2.38 Reaction times of the safety module (schematic diagram, excerpt from Fig. 2.3)
Festo – GDCP-CAMC-G-S3-EN – 1406NH – English
Cycle time
Function
typ. 125 μs
The cycle is internally synchronised to the control sampling
cycle of the basic unit, T
– recording of all inputs and outputs
– analysis of the position encoders
– filter calculation
– generation of the test pulses
– internal communication
2 ms
Fixed sampling cycle for safety functions
– calculation of the safety functions
– calculation of the logic functions
– Finite state machine, error management
– signal sequence LIN_x -> VOUT_x
. Thus an input signal is recorded at best immediately or, at the latest,
VIN_x_y
Safety Functions
Logic
Safety Function
STO
T
L
range = 100 μs – 200 μs
Sample
VOUT_x
LOUT_x
Logic
VOUT_STO_SFR
VOUT_STO_SSR
T
O
DOUT40A/B
Output Driver
+
Test Pulse Unit