Technical appendix
Error acceptance
Further requirements for the analysis of SIL position encoders
Supply voltage monitoring of the
encoder
Compliance with the operating
and ambient conditions spe
cified for the encoder
1) Sensitivity and DC in accordance with the parameterised fault limits; specification applies to factory setting
2) Position information is "static" if there is a fault => Fixed commutating position, motor at idle / voltage of a channel static
=> Commutating position changes by max +/-90° of a signal period of an encoder, motor only moves in this range
Tab. A.20 SIN/COS encoder, Hiperface encoder
Classification of the safety mode in conjunction with the SIN/COS encoder, Hiperface
encoder:
Detection of encoder fault:
Classification in accordance with
EN 61800-5-2 / EN ISO 13849-1:
246
Fault
Error detection by the
exclusion
safety module
None
Not present.
This must be ensured at
the encoder
None
Not present.
This must be ensured at
the encoder
DC > 90%
SIL2 / cat. 3 / PL d (safe positioning, incl. at rest)
and
SIL3 / cat. 3 / PL e (safe speed and acceleration)
Festo – GDCP-CAMC-G-S3-EN – 1406NH – English
Supplementary notes/
comments
The basic unit contains
regulation of the power
supply for the encoder.
In the case of error
(overvoltage, over-cur
rent), the encoder sup
ply can be switched off
functionally
The basic unit has an in
put for monitoring the
motor temperature. In
the case of error, the
drive can be switched
off functionally