2
Product description of safety module CAMC-G-S3
Term/abbreviation
LOUT_x
DRIVER + TEST PULSE GENERATOR +
FEED BACK EVALUATION
DOUT4...A / DOUT4...B
[57-0] IO_ERR
Tab. 2.73 Legend for Fig. 2.30
The output is activated by selecting one or more VOUT_x signals, which are applied to LOUT_D4x.
Each safe digital output can be configured as follows (P03.30 for DOUT40):
– permanently OFF (DOUT40A/B = 0 V),
– permanently ON (DOUT40A/B = 24 V),
– equivalent switching,
– antivalent switching.
The test pulse length can be parameterised (P03.31 for DOUT40).
You can use the outputs to monitor passive sensors using test pulses. To do this, config
ure one of the outputs to "Permanently on" and use the outputs DOUT4x A/B to supply
the switching device è Section 3.3, Sample circuits.
The following tables show the allocation of the logic signal LOUT_D4x to the output level for outputs
switching equivalently and antivalently:
Output DOUT40/41/42 Equivalent
LOUT_D40/41/42
DOUT40A/41A/42A
DOUT40B/41B/42B
Tab. 2.74 Logic signals DOUT40/41/42 equivalent
Output DOUT40/41/42 Antivalent
LOUT_D40/41/42
DOUT40A/41A/42A
DOUT40B/41B/42B
Tab. 2.75 Logic signals DOUT40/41/42 antivalent
Festo – GDCP-CAMC-G-S3-EN – 1406NH – English
Explanation
Logical outputs
Drivers, generation of test pulses and analysis
Two-channel digital outputs
Internal error signal, error 57-0
Idle state
1
24 V
24 V
Idle state
1
24 V
0 V
Safe state requested
0
0 V
0 V
Safe state requested
0
0 V
24 V
121