Product description of safety module CAMC-G-S3
Term/abbreviation
LOUT_x
DRIVER + TEST PULSE GENERATOR +
FEED BACK EVALUATION
DOUT4...A / DOUT4...B
[57-0] IO_ERR
Tab. 2.73 Legend for Fig. 2.30
The output is activated by selecting one or more VOUT_x signals, which are applied to LOUT_D4x.
Each safe digital output can be configured as follows (P03.30 for DOUT40):
– permanently OFF (DOUT40A/B = 0 V),
– permanently ON (DOUT40A/B = 24 V),
– equivalent switching,
– antivalent switching.
The test pulse length can be parameterised (P03.31 for DOUT40).
You can use the outputs to monitor passive sensors using test pulses. To do this, config­
ure one of the outputs to "Permanently on" and use the outputs DOUT4x A/B to supply
the switching device è Section 3.3, Sample circuits.
The following tables show the allocation of the logic signal LOUT_D4x to the output level for outputs
switching equivalently and antivalently:
Output DOUT40/41/42 Equivalent
LOUT_D40/41/42
DOUT40A/41A/42A
DOUT40B/41B/42B
Tab. 2.74 Logic signals DOUT40/41/42 equivalent
Output DOUT40/41/42 Antivalent
LOUT_D40/41/42
DOUT40A/41A/42A
DOUT40B/41B/42B
Tab. 2.75 Logic signals DOUT40/41/42 antivalent
Festo – GDCP-CAMC-G-S3-EN – 1406NH – English
Explanation
Logical outputs
Drivers, generation of test pulses and analysis
Two-channel digital outputs
Internal error signal, error 57-0
Idle state
1
24 V
24 V
Idle state
1
24 V
0 V
Safe state requested
0
0 V
0 V
Safe state requested
0
0 V
24 V
121