Festo CAMC-G-S3 Manual page 126

Safety module
Table of Contents

Advertisement

2
Product description of safety module CAMC-G-S3
Internal brake activation at the output [X6] is suitable for clamping units of holding brakes
with 24 V and a current consumption of max. 2 A è Technical data of brake output in the
hardware description GDCP-CMMP-AS-G3-HW-...
Alternatively, the clamping unit or holding brake can be activated via a safe digital output
(DOUT40 to DOUT42) and an external brake switching device è see examples in Section
3.3.5 and 3.3.6.
Timing diagram
Fig. 2.33 shows an example of the runtime performance when the internal brake output [X6] is switched
off and on again. The test pulses for the energised clamping unit or holding brake (vented) are also
shown. They are temporally offset.
Internal Brake
VOUT_SBC_BRK_ON
LOUT_BRK_CONTROL
X6.x BR+
X6.y BR-
Fig. 2.33 Timing diagram of the integrated brake control in the basic unit
Term/abbreviation
VOUT_SBC_BRK_ON
LOUT_BRK_CONTROL
X6.x BR+ / X6.y BR-
Tab. 2.81 Legend for Fig. 2.33
From activation of the internal brake, the following times elapse until the output pins at [X6] are
switched over:
Time delays from LOUT_BRAKE_CTRL until level change of
brake output [X6] of the basic unit
Time delay Ts
Length of the test pulses (P02.37)
Tab. 2.82 Time delays, internal brake
126
Ts < 4.0 ms
P02.37
P02.37
Explanation
Virtual output, activation of internal brake
Logical output, activation of internal brake
Signals at the contacts of the brake output in the basic unit
Ts < 4.0 ms
LOUT_BRK_CONTROL
= NOT(VOUT_SBC_BRK_ON)
Minimum
Maximum
0.0 ms
4.0 ms
0.4 ms
10.0 ms
Festo – GDCP-CAMC-G-S3-EN – 1406NH – English
Typical
2.0 ms
1.0 ms