Diagnostics
5
Ensure the director reporting the problem is connected to facility AC power and
the power switch (circuit breaker) at the rear of the director is set to the ON (up)
position. Inspect the director for indications of being powered on, such as:
Is the director powered on?
YES
6
At the director, inspect the amber LED at the top of each CTP card.
Is the amber LED illuminated on both CTP cards?
NO
7
The director-to-HAFM appliance Ethernet link failed. Perform the following:
1. At the physical map, right-click the icon with the grey square and exclamation
2. Choose the Element Manager option from the menu. The Hardware View
94
At the front bezel, an illuminated power LED (green) or system error LED
(amber).
An illuminated green LED on the active CTP card, and illuminated green
PWR OK LEDs on both power supplies.
Audio emanations and airflow from cooling fans.
NO
A power distribution problem is indicated. Go to
Distribution
YES
Failure of both CTP cards is indicated. Go to
Failure
Analysis" on page 107. Exit MAP.
mark representing the director or switch reporting the problem. A pop-up
menu displays.
displays and the following occurs:
A grey square displays at the alert panel.
No FRUs are visible for the director.
The Director 2/140 Status table is yellow, the Status field displays No
Link, and the Reason field displays an error message.
Analysis" on page 69. Exit MAP.
"MAP 0100: Power
"MAP 0500: FRU
Director 2/140 Service Manual