Diagnostics
A faulty power LED is indicated, but director and Fibre Channel port operation is
not disrupted. The LED is connected to the circuitry in a fan module, and the
module must be removed and replaced
page 250). Exit MAP.
30
Is the system error LED (amber) at the director front bezel blinking?
YES
31
Unit beaconing is enabled for the director.
1. Consult the customer and next level of support to determine the reason unit
2. Disable unit beaconing.
Was unit beaconing enabled because a director failure or degradation was
suspected?
YES
Go to
32
Is the system error LED (amber) at the director front bezel illuminated?
YES
33
Check FRUs (UPM cards, CTP cards, SBAR assemblies, power supplies, and fan
modules) for failure symptoms.
58
NO
Go to
step
32.
beaconing is enabled.
a. At the Hardware View, right-click the front bezel graphic (away from a
FRU). A menu displays.
b. Click Enable Unit Beaconing. The check mark disappears from the box
adjacent to the option, and unit beaconing is disabled.
NO
The director is operational. Exit MAP.
step
24.
NO
The director is operational. Verify operation at the HAFM appliance.
Go to
step
3.
("RRP: Redundant Fan
Director 2/140 Service Manual