An SBAR assembly failed and must be removed and replaced
SBAR
Did SBAR assembly replacement solve the problem?
NO
Contact the next level of support. Exit MAP.
10
Is fault isolation being performed at the HAFM appliance?
YES
11
Is a blinking red and yellow diamond (failed FRU indicator) overlaying a fan
module graphic at the Hardware View?
NO
12
Is a blinking red and yellow diamond (failed FRU indicator) overlaying a CTP
card graphic at the Hardware View?
NO
Director 2/140 Service Manual
Assembly" on page 247).
This procedure is concurrent and can be performed while director power is on.
Perform the data collection procedure as part of FRU removal and
replacement.
YES
The director is operational. Exit MAP.
NO
Fault isolation is being performed at the Embedded Web Server
interface. Go to
YES
A fan module failure is indicated. Go to
YES
A CTP card failure is indicated. Go to
step
18.
("RRP: Redundant
step
5.
step
7.
Diagnostics
111