HP storageworks director 2/140 Service Manual page 135

Hide thumbs Also See for storageworks director 2/140:
Table of Contents

Advertisement

Continue to the next step.
44
Ensure the director reporting the problem is connected to facility AC power and
the power switch (circuit breaker) at the rear of the director is set to the ON (up)
position. Inspect the director for indications of being powered on, such as:
Is the director powered on?
YES
45
Inspect UPM card operational states at the Embedded Web Server interface.
1. At the View panel, click the FRU Properties tab. The View panel (FRU
2. Inspect the Status fields for UPM cards. Scroll down the View panel as
Does the Status field display a Failed message for a UPM card?
NO
Director 2/140 Service Manual
AC power distribution in the director failed, or AC power was disconnected.
Both of the director's CTP cards failed.
At the front bezel, an illuminated power LED (green) or system error LED
(amber).
An illuminated green LED on the active CTP card.
At least one green PWR OK LED illuminated on a power supply.
Audio emanations and airflow from cooling fans.
NO
Analysis for an Ethernet link, AC power distribution, or dual CTP
card failure is not described in this MAP. Go to
MAP" on page 45. If this is the second time at this step, contact the
next level of support. Exit MAP.
Properties tab) displays.
necessary.
YES
A UPM card failure is indicated. Go to
Diagnostics
"MAP 0000: Start
step
7.
135