Diagnostics
9
A power supply failed POSTs (indicated by a 06 FRU code) and must be removed
and replaced
Note:
To avoid director overheating, a power supply must be replaced within five minutes.
Did power supply replacement solve the problem?
NO
Contact the next level of support. Exit MAP.
10
A UPM card failed POSTs (indicated by a 08 through 0F FRU code) and must be
removed and replaced
Did UPM card replacement solve the problem?
NO
Contact the next level of support. Exit MAP.
11
POST/IPL diagnostics detected a firmware failure (as indicated by an event code
411) and performed an online dump. All Fibre Channel ports reset after the failure
and devices momentarily log out, log in, and resume operation.
Perform the data collection procedure and return the information to HP for
analysis by third-level support personnel. Exit MAP.
82
("RRP: Redundant Power
This procedure is concurrent and can be performed while director power is on.
Perform the data collection procedure as part of FRU removal and
replacement.
Do not remove a power supply unless a replacement is immediately available.
YES
The director is operational. Exit MAP.
("RRP: UPM
This procedure is concurrent and can be performed while director power is on.
Perform the data collection procedure as part of FRU removal and
replacement.
YES
The director is operational. Exit MAP.
Supply" on page 241).
Card" on page 231).