Diagnostics
Is the director powered on?
YES
28
At the director, inspect the amber LED at the top of each CTP card.
Is the amber LED illuminated on both CTP cards?
NO
29
Either a director-to-PC Internet link problem (Internet too busy or IP address
typed incorrectly) or a director Ethernet port failure is indicated.
1. Wait approximately five minutes, then attempt to log in to the director again.
2. At the Netsite field (Netscape Navigator) or Address field (Internet
3. Type the username and password obtained in
Is the Embedded Web Server interface operational with the View panel
displayed?
NO
Failure of the CTP card's Ethernet port is indicated. Go to
Failure
106
Audio emanations and airflow from cooling fans.
NO
A power distribution problem is indicated. Go to
Distribution
YES
Failure of both CTP cards is indicated. Go to
Failure
Analysis" on page 107. Exit MAP.
Explorer), type http://xxx.xxx.xxx.xxx, where
xxx.xxx.xxx.xxx is the IP address of the director (obtained in
0000: Start
MAP" on page 45). The Username And Password Required dialog
box displays.
page 45 and click OK. If the View panel does not display, wait five minutes
and perform this step again.
YES
The director-to-Web server PC connection is restored and is
operational. Exit MAP.
Analysis" on page 107. Exit MAP.
Analysis" on page 69. Exit MAP.
"MAP 0100: Power
"MAP 0500: FRU
"MAP 0000: Start
MAP" on
"MAP 0500: FRU