Analysis for an Ethernet link or dual CTP card failure is not described in this
MAP. Go to
step, contact the next level of support. Exit MAP.
25
Is the Embedded Web Server interface operational?
NO
26
A Page cannot be found, Unable to locate the server,
HTTP 404-file not found, or other similar message displays. The
message indicates the Web browser PC cannot communicate with the director
because:
Continue to the next step.
27
Ensure the director reporting the problem is connected to facility AC power and
the power switch (circuit breaker) at the rear of the director is set to the ON (up)
position. Inspect the director for indications of being powered on, such as:
Is the director powered on?
YES
Analysis for an Ethernet link or dual CTP card failure is not described in this
MAP. Go to
step, contact the next level of support. Exit MAP.
Director 2/140 Service Manual
"MAP 0000: Start
YES
Go to
step
28.
The director-to-PC Internet link could not be established.
AC power distribution in the director failed, or AC power was disconnected.
Both of the director's CTP cards failed.
At the front bezel, an illuminated power LED (green) or system error LED
(amber).
An illuminated green LED on the active CTP card.
At least one green PWR OK LED illuminated on a power supply.
Audio emanations and airflow from cooling fans.
NO
Go to
step
14.
"MAP 0000: Start
MAP" on page 45. If this is the second time at this
MAP" on page 45. If this is the second time at this
Diagnostics
77