Installing The Front Door On A Ptx5000 In An Open-Frame Rack - Juniper PTX5000 Hardware Manual

Packet transport router
Hide thumbs Also See for PTX5000:
Table of Contents

Advertisement

Installing the Front Door on a PTX5000 in an Open-Frame Rack

You can install a door over the front card cage of the PTX5000. Captive thumbscrews secure the door in
a closed position.
NOTE: If you plan to install the PTX5000 in an open-frame rack, you can install the door before
the chassis is mounted in the rack. However, this procedure assumes that the router has been
installed in the rack and grounded. If you install the door before grounding the router, ensure
that you use proper site grounding.
Before you begin, ensure that you have the following parts and tools available to install the front door
on a PTX5000 in an open-frame rack.
• Electrostatic discharge (ESD) grounding strap
• Phillips (+) screwdriver, number 2
To install the front door on a PTX5000 in an open-frame rack (see
142 on page
290):
1. Attach an electrostatic discharge (ESD) grounding strap to your bare wrist, and connect the strap to
the approved ESD site grounding point.
2. Using the provided UNC 12–24 screws, attach the long mounting brackets to the rear of each front-
mounting flange. Insert screws only at the top and bottom of each bracket. The top screw should be
inserted at the third front-mounting flange hole from the top of the chassis. Line up the edge of the
Figure 141 on page 288
287
and
Figure