Ptx5000 Ac And Dc Pdu Electrical And External Circuit Breaker Specifications - Juniper PTX5000 Hardware Manual

Packet transport router
Hide thumbs Also See for PTX5000:
Table of Contents

Advertisement

• Bare conductors shall be coated with an antioxidant before crimp connections are made.
• Plated areas that are electrically connected to the grounding conductor shall be cleaned and free of
contaminants before the connection is made.
SEE ALSO
Tools and Parts Required to Ground the PTX5000 | 220
Connecting the PTX5000 to Earth Ground | 220
PTX5000 AC and DC PDU Electrical and External Circuit Breaker
Specifications
Table 62 on page 166
lists the AC PDU electrical and external circuit breaker specifications.
Table 62: PTX5000 AC PDU Electrical and External Circuit Breaker Specifications
PDU
Normal Capacity Three-
phase AC Delta PDU
(PDU-PTX-AC-D)
Normal Capacity Three-
phase AC Wye PDU
(PDU-PTX-AC-W)
High Capacity Delta AC
PDU (PDU2-PTX-AC-D)
with 60 A power cord
High Capacity Delta AC
PDU (PDU2-PTX-AC-D)
with 100 A power cord
Maximum
Cable
Current
Amp
Drawn
Rating
48 A
60 A
32 A
32 A
48 A
60 A
80 A
80 A
External
Operational
Circuit
Voltage
Breaker/
Fuse
60 A
200 V–240 V
32 A
200 V–240 V
60 A
200 V–240 V
80 A
200 V–240 V
Feeds
Plug
per PDU
Rating
1
60 A
1
32 A
1
60 A
1
100 A