screws on the metal retaining bracket to secure the AC power cord to the PDU (see
page
232).
Figure 98: Connecting Power to a Three-Phase Wye AC PDU
7.
Connect the wires to the AC terminal block on the three-phase wye AC power supply
page
233). Using a 1/5-in. (5.5-mm) slotted screwdriver, loosen each of the input terminals or
grounding point screws, insert each wire into the grounding point or input terminal, and tighten the
screw.
a. Insert the wire labeled GND into the grounding point.
b. Insert the wire labeled L1 into the L1 input terminal.
c. Insert the wire labeled L2 into the L2 input terminal.
d. Insert the wire labeled L3 into the L3 input terminal.
e. Insert the wire labeled N into the N input terminal
232
Figure 98 on
(Figure 99 on