Juniper PTX5000 Hardware Manual page 244

Packet transport router
Hide thumbs Also See for PTX5000:
Table of Contents

Advertisement

226
metal AC wiring compartment. Using a number 2 Phillips (+) screwdriver, use the four screws on the
metal retaining bracket to secure the AC power cord to the PDU (see
Figure 91 on page
226).
Figure 91: Connecting Power to a Three-Phase Delta AC PDU
7.
Connect the wires to the AC terminal block on the three-phase delta AC PDU
(Figure 92 on page
227). Using a 1/5-in. (5.5-mm) slotted screwdriver, loosen each of the input terminals or grounding
point screws, insert each wire into the grounding point or input terminal, and tighten the screw.
a. Insert the wire labeled GND into the grounding point.
b. Insert the wire labeled L1 into the L1 input terminal.
c. Insert the wire labeled L2 into the L2 input terminal.