Using a number 2 Phillips (+) screwdriver, loosen the two captive screws to the metal wiring
compartment door. Open the door of the metal wiring compartment. Disconnect the wires from the
AC terminal block on the High Capacity Wye AC PDU
screwdriver, loosen the input terminal screws and the grounding point screw, and remove each wire
from the input terminal points and the grounding point.
a. Remove the wire labeled L3 from the L3 input terminal.
b. Remove the wire labeled L2 from the L2 input terminal.
c. Remove the wire labeled L1 from the L1 input terminal.
d. Remove the wire labeled GND into the grounding point.
Figure 204: Disconnecting AC Power Wires from a High Capacity Wye AC PDU
8.
Using a number 2 Phillips (+) screwdriver, loosen the screws that secure the metal retaining bracket
and AC power cord to the PDU. While gently removing the wires of the AC power cord from the
(Figure
39). Using 7/32-in. (5.5-mm) slotted
396