Juniper PTX5000 Hardware Manual page 266

Packet transport router
Hide thumbs Also See for PTX5000:
Table of Contents

Advertisement

c. Push the wires of the AC power cord into the area for the metal retaining bracket, and pull the
wires to the left toward the metal AC wiring compartment.
d. Using a number 2 Phillips (+) screwdriver, use the four captive screws on the metal retaining
bracket to secure the AC power cord to the PDU (see
Figure 115: Connecting Power to a High Capacity Wye AC PDU
8.
Connect the wires to the AC terminal block on the High Capacity Wye AC PDU (see
page
249). Using a 1/5-in. (5.5-mm) slotted screwdriver, loosen each of the input terminal screws
and the grounding point screw, insert each wire into the grounding point or input terminal, and
tighten the screw.
a. Insert the neutral wire labeled GND into the grounding point.
b. Insert the wire labeled L1 into the L1 input terminal.
c. Insert the wire labeled L2 into the L2 input terminal.
d. Insert the wire labeled L3 into the L3 input terminal.
e. Insert the wire labeled N into the N input terminal.
Figure 115 on page
248).
248
Figure 116 on

Advertisement