DC Power Lugs
The accessory box shipped with the PTX5000 includes 0-AWG and 4-AWG cable lugs . The cable lugs
are dual hole, and sized to fit 1/4-20 UNC terminal studs at 15.86-mm (0.625-in.) center line.
on page 113
indicates the cable lug specifications for each type of PDU.
You attach these cable lugs to the DC terminal studs of each input power tray of the 60-A and 120-A
PDUs and to the terminal studs (16 for eight PSMs) in the front of the High Capacity DC PDU. The 0-
AWG cable lug is also used for grounding the PTX5000.
Table 42: DC Power Cable Specifications
PDU
60-A
120-A
High Capacity (60-A)
Cable Lugs
2
6-AWG (13.3 mm
) minimum
2
4-AWG (21.2 mm
) maximum
See
Figure 57 on page
114.
2
0-AWG (53 mm
),
See
Figure 56 on page
114.
2
6-AWG (13.3 mm
) minimum
2
4-AWG (21.2 mm
) maximum
See
Figure 57 on page
114.
113