Upgrading The Ptx5000 To A High Capacity Power System; Upgrading To The High Capacity Ac Power System - Juniper PTX5000 Hardware Manual

Packet transport router
Hide thumbs Also See for PTX5000:
Table of Contents

Advertisement

Installing the High Capacity PSM Sleeves | 457
Upgrading the PTX5000 to a High Capacity Power
System
IN THIS SECTION

Upgrading to the High Capacity AC Power System | 449

Upgrading to the High Capacity DC Power System | 454
Installing the High Capacity PSM Sleeves | 457
Upgrading to the High Capacity AC Power System
Before you upgrade a PTX5000 to the High Capacity AC power system from a normal-capacity power
system:
• Ensure that the No Redundant Power for System alarm is not displayed when you run the show chassis alarms
operational-mode CLI command.
If the No Redundant Power for System alarm is displayed, see
System Power Zones" on page 182
zones for normal-capacity PSMs. Modify your hardware configuration so that the PTX5000 power
system is redundant. Once redundant power is configured and the alarm is no longer displayed, you
can begin the upgrade procedure.
• Ensure that the PTX5000 is running Junos OS release 14.1R2 or a later 14.1 release, or Junos OS
release 14.2 or later.
NOTE: If you are upgrading from normal-capacity Delta or Wye AC PDUs, you must begin this
procedure with the left PDU when viewed from the rear of the chassis (labeled PDU1 on the
chassis).
"Understanding Normal-Capacity Power
for more information about PTX5000 redundancy and power
449