9.
Using a number 2 Phillips (+) screwdriver, tighten the four captive screws on the metal retaining
bracket to secure the AC power cord to the PDU.
Figure 186: Connecting the Metal Retaining Bracket and AC Power Cord to the Three-Phase Wye
PDU
10. Connect the wires to the AC terminal block on the three-phase wye AC PDU
375). Using a 1/5-in. (5.5-mm) slotted screwdriver, loosen the input terminal or grounding point
screw, and insert each wire into the grounding point or input terminal, and tighten the screw.
a. Insert the wire labeled GND into the grounding point.
b. Insert the wire labeled L1 into the L1 input terminal.
c. Insert the wire labeled L2 into the L2 input terminal.
d. Insert the wire labeled L3 into the L3 input terminal.
(Figure 187 on page
374