CAUTION: To avoid damage to the PDU, do not connect the neutral wire to the
L1, L2, or L3 input terminal.
Figure 116: Connecting Power to the High Capacity Wye AC PDU
9.
Verify that the AC power wiring connections are correct.
10. Close the door to the metal AC wiring compartment, and use a number 2 Phillips (+) screwdriver to
tighten the two captive screws to secure the door to the metal AC wiring compartment.
11. Verify that the AC power cord does not touch or block access to PTX5000 components, and that it
does not drape where people could trip on it.
12. Repeat the procedure for the other High Capacity Wye AC PDU.

Connecting Power to the PTX5000 High Capacity Single-Phase AC PDUs

The high-capacity single-phase AC PDU accepts eight single-phase 30-A or eight single-phase 20-A,
200–250 VAC L-L input power. One 30-A or 20-A input power provides dedicated input power to each
PSM.
249