CAUTION: Do not leave a PDU slot empty for more than a short time while the
PTX5000 is operational. For proper airflow, the PDU must remain in the chassis or a
blank panel must be used in an empty slot.

Installing a PTX5000 High Capacity DC PDU

Each High Capacity DC PDU without the PSMs weighs approximately 64.5 lb (29.3 kg). To install a PDU:
1.
Make sure that the voltage across the DC power source cable leads is 0 V and that there is no
chance that the cables might become active during installation.
2.
Verify that power switch on the PDU is in the standby
(
) position.
3.
Verify that the DC power input cables are disconnected.