PTX5000 Site Guidelines and Requirements

IN THIS SECTION

PTX5000 Environmental Specifications | 162

General Site Guidelines | 163
PTX5000 Chassis Grounding Cable and Lug Specifications | 164
PTX5000 AC and DC PDU Electrical and External Circuit Breaker Specifications | 166
PTX5000 Clearance Requirements for Airflow and Hardware Maintenance | 168
PTX5000 Physical Specifications | 169
Site Electrical Wiring Guidelines | 173
Rack Requirements for the PTX5000 | 174
PTX5000 Environmental Specifications
Table 60 on page 162
specifies the environmental specifications required for normal PTX5000
operation. In addition, the site should be as dust-free as possible.
Table 60: PTX5000 Environmental Specifications
Description
Altitude
Relative humidity
Temperature
Seismic
Value
No performance degradation to 10,000 ft (3048 m)
Normal operation ensured in relative humidity range of 5% to 90%, noncondensing
Normal operation ensured in temperature range of 32°F (0°C) to 104°F (40°C)
Nonoperating storage temperature in shipping crate: –40°F (–40°C) to 158°F (70°C)
Designed to meet Telcordia Technologies Zone 4 earthquake requirements