Operating Access Levels; Operating Access Level 1; Operating Access Level 2; Operating Access Level 3A - Siemens XC1001-A Installation And Maintenance Manual

Extinguishing control unit xc10 series
Hide thumbs Also See for XC1001-A:
Table of Contents

Advertisement

Operating access levels

10
Operating access levels
10.1

Operating access level 1

10.2

Operating access level 2

10.3

Operating access level 3A

10.4

Operating access level 3B

56
Building Technologies
Fire Safety
XC100x-A equipment operation is organised in several operating access levels.
This level gives access to:
-
silence buzzer (see programming options in step 56)
-
led test
-
fault detailed display
-
alarm counter display (XC1003-A and XC1005-A only)
This operating access level gives access, after code input on keyboard (4 2 3 3 by
default or personalised) or by key (option), to the following controls:
-
silence buzzer (see programming options in step 56)
-
silence / re-sound sounders
-
automatic blocked / automatic and manual blocked
-
disable / enable
-
test of zones 1...4
-
reset
-
test of sounders, warning panels, RT-alarm and RT-fault
- Operating access level 2 is automatically disabled after 4 minutes if no handling is carried out for
this period
- Operating access level 2 can be manually swiched back to level 1 after the same code input (For
customers who don't want to wait 4 minutes)
This operating access level gives access, after code input on the keyboard, to the
"system test" function (see paragraph 15.6).
This operating access level gives access, after removing the front plastic cover and
codes input on the keyboard, to:
-
user functions programming
-
outputs individual test
-
checksum display
-
alarm counter display
-
maintenance PC connection (no code is needed)
A6V10257473_e_en_--
2015-03-04

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xc1005-aXc1003-a

Table of Contents