Pn421
Analog Monitor Output Selection
Setting
0 to 2
range
Select the analog monitor output voltage direction.
Set
value
0
-10 to 10 V
1
0 to 10 V
2
0 to 10 V
When monitor type is motor speed and gain of conversion is 500 (1 V = 500 r/min)
Pn422
Analog Input 1 Offset
Setting
−5,578 to 5,578
range
Adjust the offset of the speed command input (REF: CN1 pin 14).
The offset amount is approx. the set value times 0.359 mV.
There are 2 ways to adjust the offset.
· Manual adjustment
· Automatic adjustment
The manual adjustment is as follows:
· To adjust the offset for individual drivers, accurately input 0 V to the speed command input/torque command input
(REF/TREF1) (or connect to the signal ground), and then set this parameter so that the motor does not rotate.
· If you use a position loop in the host device, set this parameter so that there are no
accumulated pulses at servo lock stop status.
The automatic adjustment is as follows:
This parameter will be automatically set when automatic offset adjustment is executed. Refer to
"Analog Input Automatic Offset Adjustment" (P.9-27) for the automatic offset adjustment method.
Accurax G5 AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
8-5 Interface Monitor Setting Parameters
Unit
Output range
Unit
0.359 mV
Default
0
setting
Data output
Output voltage [V]
10 V
Motor
speed
0 V
−5,000
5,000 [r/min]
−10 V
Output voltage [V]
10 V
Motor
speed
−5,000
0 V
5,000 [r/min]
−10 V
Output voltage [V]
10 V
5 V
Motor
speed
0 V
0
2,500 [r/min]
−2,500
−10 V
Default
0
setting
All
Power OFF
and ON
8
All
Power OFF
and ON
8-39