Safety Input Circuit
External power supply
12 VDC ± 5% to
24 VDC ± 5%
Signal level
ON level: 10 V or more
OFF level: 3 V max.
EDM Output Circuit
Servo Drive
Accurax G5 AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
SF1+
SF1−
SF2+
SF2−
10 Ω
7 −EDM
X
8 +EDM
Di
Di: Surge voltage prevention diode
(Use a high-speed diode.)
3-1 Driver Specifications
Servo Drive
4
4.7 kΩ
1.0 kΩ
3
4.7 kΩ
6
1.0 kΩ
5
External power supply
12 to 24 VDC
Maximum service voltage: 30 VDC or less
Maximum output current: 50 mA max.
Photocoupler
input
Photocoupler
input
3
3-53