Pn101
Speed Loop Gain
Setting
1 to 32,767
range
Default settings:
(1) Pn101 = 180 - For 200V drives of 1Kw or upper and 400V drives
(2) Pn101 = 270 - For 200V drives of less than 1 Kw
Determine speed loop responsiveness.
The setting for the speed loop gain must be increased to increase the position loop gain and
improve the responsiveness of the entire servo system. Setting too high, however, may result in
vibration.
The setting unit for Pn101 will be Hz if the Inertia Ratio (Pn004) is set correctly.
When the speed loop gain is changed, the response is as shown in the following diagram.
Motor speed
Pn102
Speed Loop Integral Time Constant
Setting
1 to 10,000
range
Default settings:
(1) Pn102 = 310 - For 200V drives of 1Kw or upper and 400V drives
(2) Pn102 = 210 - For 200V drives of less than 1 Kw
Set the speed loop integration time constant.
The smaller the set value, the faster the error will come close to 0 when stopping. Set to 9,999 to
maintain integration. Set to 10,000 to invalidate the effect of integration.
When the speed loop integral time constant is changed, the response is as shown in the
following diagram.
Motor speed
Accurax G5 AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
Unit
0.1 Hz
Overshooting occurs if the speed loop gain is high.
(Vibration occurs if the gain is too high.)
Speed loop gain is low.
Unit
0.1 ms
Overshooting occurs if the speed loop integral
time constant is small.
Speed loop integral
time constant is large.
8-2 Gain Parameters
See
Default
Power OFF
Note
setting
and ON
below
See
Default
Power OFF
Note
setting
and ON
below
All
Time
8
All
Time
8-11