Details of output signals

Module error clear request (YE)
This signal is used to clear the minor error that has occurred on the own station.
• On: Minor error clear request
• Off: 
If this signal turns on when an own station error has occurred, the following operations are executed.
• The latest error code is cleared.
• The ERR LED is turned off.
• 'Own Error' (XE) is turned off.
Performed by the RJ71GN11-EIP
Performed by a program
'Module error clear request' (YE)
'Own error' (XE) and ERR LED
Latest error code
(1) Error occurrence
(2) Elimination of error cause
PING test execution request (Y12)
Turn this signal off and on to execute a PING test.
• Off to on: PING test execution request
• On to off: PING test completion request
Turning on 'PING test execution request' (Y12) clears 'PING test response area' (Un\G7340052 to Un\G7340064).
Turning off 'PING test execution request' (Y12) turns 'PING test completion' (X12) on and off.
Performed by the RJ71GN11-EIP
Performed by the program
'PING test execution request'
(Y12)
'PING test completion' (X12)
'PING test request area'
(Un\G7340048 to Un\G7340051)
'PING test response result area'
(Un\G7340052 to Un\G7340064)
OFF
OFF
(1)
0
ON
OFF
OFF
ON
(2)
ON
Error code
OFF
ON
Request data setting
Request data setting
0
PING test result
OFF
OFF
OFF