Instance attribute (instance ID: 01H)
Attribute
Access
ID
(: Available, :
Not available)
Get
Set
1
2
3
4
5
6
8
9
*1
13
*1 The setting data is saved to non-volatile memory.
■Details of interface status
Bit
Description
0 to 3
Interface Configuration Status
4
Mcast Pending
Name
Status
Configuration Capability
Configuration Control
Physical Link
Path size
Object
Path
Interface
IP Address
Configuration
Network Mask
Gateway
Address
Name Server
Name Server 2
Domain Name
Host Name
TTL Value
MCast Config
Alloc Control
Reserved
Num Mcast
Mcast Start Addr
Encapsulation Inactivity Timeout
Value
Fixed to 2 (to set the IP address acquired from the parameter settings)
• 0: No changes to TTL Value and Mcast Config
• 1: In the wait-for-restart state due to changes to TTL Value and Mcast Config
Data
Description
type
DWORD
Interface status
DWORD
Interface capability flag
DWORD
Interface control flag
UINT
Path size of physical link object
Padded
Logical segment that identifies
EPATH
the physical link object
UDINT
IP address of the device
UDINT
Network mask of the device
UDINT
Default gateway address
UDINT
Primary name server
UDINT
Secondary name server
STRING
Default domain name
STRING
Host name
USINT
TTL value for EtherNet/IP
multicast packets
USINT
IP multicast address setting
USINT
Reserved
UINT
Number of IP multicast addresses
to assign for EtherNet/IP
UDINT
First multicast address from
which to start assignment
UINT
Setting of the time until the TCP
connection or DTLS session
closes
(unit: seconds)
14 MESSAGE COMMUNICATION SUPPORT COMMANDS
Setting value (Set)/
stored value (Get)
Page 357 Details of
interface status
Page 358 Details of
interface capability flag
Page 358 Details of
interface control flag
0002H
• 0: 20H
• 1: F6H
• 2: 24H
• 3: 01H
Set values of parameters
00000000H
00000000H
" " (null character)
" " (null character)
1 to 255
Value on the left
00H
1 to 32
Value on the left
• 1 to 3600
0 is invalid.
(Default: 120)