Error
Error definition and causes
code
D213H
• The command of transient transmission
is incorrect.
• The CC-Link IE TSN/CC-Link IE Field
diagnostics was used for the network to
which the relay receiving station
belongs.
• The module at the connection
destination does not support this
function.
D214H
The data length of transient transmission is
incorrect.
D239H
SLMP transmission failed.
D240H
The network number specification of the
dedicated instruction is incorrect.
D241H
The target station number of the dedicated
instruction is incorrect.
D242H
The command code of the dedicated
instruction is incorrect.
D243H
The channel specified in the dedicated
instruction is incorrect.
D244H
The transient data is incorrect.
D245H
The target station number of the dedicated
instruction is incorrect.
D247H
When the dedicated instruction was
executed, response from the target station
was received twice.
D249H
The target station CPU type of the
dedicated instruction is incorrect.
D24AH
The arrival monitoring time specification of
the dedicated instruction is incorrect.
19 LIST OF ERROR CODES
422
19.1 Error Codes When a Module Error Occurs
Action
• Execute the instruction again after correcting the request command at the
transient request source.
• Review the connection destination so that the CC-Link IE TSN/CC-Link IE
Field diagnostics is used for the network to which the relay sending station
belongs.
• Check the manual for the module at the connection destination and check
the status of support for this function. If not supported, update the
firmware version to the one that supports this function.
Execute the instruction again after correcting the data length at the transient
request source, and retry the operation.
• Retry the operation after a while.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the network number at the
request source of the dedicated instruction.
• If the request source is on another network, check if "Routing Settings" of
CPU parameters are set correctly, and take action.
• Execute the instruction again after correcting the target station number at
the request source of the dedicated instruction.
• If the request source is on another network, check if "Routing Settings" of
CPU parameters are set correctly, and take action.
• Execute the instruction again after correcting the command code at the
request source of the dedicated instruction.
• If the request source is on another network, check if "Routing Settings" of
CPU parameters are set correctly, and take action.
• Execute the instruction again after correcting the used channel within the
allowable range at the request source of the dedicated instruction.
• If the request source is on another network, check if "Routing Settings" of
CPU parameters are set correctly, and take action.
• Execute the instruction again after correcting the transient data at the
transient request source.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the target station number at
the request source of the dedicated instruction.
• If the request source is on another network, check if "Routing Settings" of
CPU parameters are set correctly, and take action.
• Check the network status using the CC-Link IE TSN/CC-Link IE Field
diagnostics of the engineering tool, and take action.
• Check if the switching hub and the Ethernet cables at the request source
are connected properly.
• If the request source is on another network, check if "Routing Settings" of
CPU parameters are set correctly, and take action.
• Execute the instruction again after correcting the CPU type of the target
station at the request source of the dedicated instruction.
• If the request source is on another network, check if "Routing Settings" of
CPU parameters are set correctly, and take action.
• Execute the instruction again after correcting the arrival monitoring time at
the request source of the dedicated instruction.
• When the own station, target station, or relay station detected an error,
identify the cause of the error and take action.
• Execute the instruction again after lower the transient transmission usage
frequency.
• Check if the switching hub and the Ethernet cables at the request source
are connected properly.
Detailed
information 1
Detailed
information 2