6
PROCEDURES BEFORE OPERATION
This chapter describes the procedures before operation.
Procedures for using CC-Link IE TSN
1.
Network configuration
Configure the system and set the parameters which are required for start-up.
• Wiring ( Page 70 WIRING)
• Parameter settings ( Page 73 Parameter Settings for CC-Link IE TSN)
2.
Network diagnostics
Use CC-Link IE TSN/CC-Link IE Field diagnostics to check that cables are connected properly and that modules are
communicating correctly with the set parameters.
For details, refer to the following.
Page 372 CC-Link IE TSN/CC-Link IE Field Diagnostics
3.
Programming
Create a program. For details, refer to the following.
Page 215 PROGRAMMING
• When multiple slave stations and the master station are powered on simultaneously, the startup time of the
slave stations may vary. In such a case, the networks are connected in turn, resulting the time may be
longer to complete data links at all stations. Power on all slave stations, and then, power on the master
station to prevent this case.
• When not using EtherNet/IP, write the module extension parameter file with the default settings. If the
module extension parameters do not exist, a moderate error will occur.
Procedures for using EtherNet/IP
1.
Network configuration
Configure the system and set the parameters which are required for start-up.
• Wiring ( Page 70 WIRING)
• Parameter settings ( Page 112 EtherNet/IP Parameter Settings)
2.
Network status check
Check the LED and buffer memory to check whether communication is normally performed. For details, refer to the following.
Page 66 PART NAMES
Page 385 Checking the Status of EtherNet/IP
3.
Programming
Create a program. For details, refer to the following.
Page 297 PROGRAMMING
6 PROCEDURES BEFORE OPERATION