Protocol information
■Protocol information (Un\G1294016 to Un\G1294031)
Address
Un\G1294016
Un\G1294017
Un\G1294018
Un\G1294019
Un\G1294020
Un\G1294021
Un\G1294022 to Un\G1294031
*1 The protocol version is automatically set according to the system configuration.
While the system is operating with the protocol version 2.0, if a device that supports protocol version 1.0 attempts to join, the joining
station does not establish a data link.
CC-Link IE TSN Class A device connection
Protocol version 1.0
Yes
None
Name
Protocol operating status
Write request
Protocol setting
Write execution status
Setting result
Protocol setting status
System area
Protocol version 2.0
Description
The operating status of the protocol is stored. 0:
Operating protocol not determined or CC-Link IE
TSN Class settings set to CC-Link IE TSN Class B
only 1: Operating with protocol version 1.0 2:
Operating with protocol version 2.0
Write the protocol setting to the module.
0: Do not write
1: Write
Set the operating protocol.
*1
0: Automatic setting
1: Protocol version 1.0 fixed
2: Protocol version 2.0 fixed
The write execution status of writing to the module
is stored.
0: Write not executed, or write execution in
progress
1. Write execution complete
The setting result is stored.
0: Completed successfully
Other than 0: Completed with an error (error code)
The protocol setting held by the module is stored.
0: Automatic setting (factory default)
1: Protocol version 1.0 fixed
2: Protocol version 2.0 fixed
Operating protocol version
1.0
2.0
Appendix 3 Buffer Memory
A
APPX
477