Details of remote output signals

FPGA control start request
■Device number
Name
FPGA control start request
■Description
Use to start FPGA control.
If FPGA controlling flag (RX0) is OFF, FPGA control is stopped.
Turning on FPGA control start request (RY0) starts FPGA control.
When FPGA control automatic start setting is set to "Enable", FPGA control starts automatically when the module power
supply is turned on. It is not necessary to turn on FPGA control start request (RY0).
For the timing of turning on and off FPGA control start request (RY0), refer to the following.
Page 469 FPGA controlling flag
FPGA control stop request
■Device number
Name
FPGA control stop request
■Description
Use to stop FPGA control.
When FPGA control is stopped by turning and on FPGA control stop request (RY1), operations such as digital input/output, A/
D conversion, and D/A conversion are stopped. The values of FPGA register areas that monitor the digital input and analog
input are also cleared. ( Page 502 FPGA register)
For the timing of turning on and off FPGA control stop request (RY1), refer to the following.
Page 469 FPGA controlling flag
Device number
RY0
Device number
RY1