Gateway Parameter Settings
With gateway parameter settings, the Ethernet-equipped module can communicate with external devices on other Ethernet
networks via a router and gateway. One default router and up to eight routers can be set.
Item
Gateway Other Than Default Gateway
Gateway Information
No.1 to No.8
Set the default gateway when communicating via the default gateway. ( Page 75 Station No./IP Address
Setting,  Page 113 Own Node Settings)
■Gateway IP Address
When communicating with an external device on another Ethernet network through a gateway other than the default gateway,
set the IP address of the gateway. (Setting range: 0.0.0.1 to 223.255.255.254)
Set a value that satisfies the following conditions.
• The class of the IP address is A, B, or C.
• The subnet address of the gateway is the same as that of the CC-Link IE TSN Plus module on the own station.
• The host address part is not a sequence of "0" or "1".
• When the CC-Link IE TSN Plus module communicates with an external device on another Ethernet network
by Passive open, communication is possible without gateway parameter settings.
• In a system where the Proxy router is used, the gateway parameter settings are not required.
8 PARAMETER SETTINGS
94
8.1 Parameter Settings for CC-Link IE TSN
Description
Set to communicate with an external device on the other Ethernet via a
router.
Set the information of the gateway other than the default gateway.
• Gateway IP Address ( Page 94 Gateway IP Address)
• Subnet Address ( Page 95 Subnet Address)
Setting range
• Use
• Not Use
(Default: Not Use)