Setting the CC-Link IE TSN Plus module (target)
Connect the engineering tool to the target-side CPU module and set the parameters.
1.
Set the CPU module and add the CC-Link IE TSN Plus module. The setting method of the CPU module and addition
method of the CC-Link IE TSN Plus module are the same as those of the CC-Link IE TSN Plus module (originator). (
Page 320 Setting the CC-Link IE TSN Plus module (originator))
2.
Set the items in "Basic Settings" as follows.
[Navigation window]  [Parameter]  [Module Information]  [RJ71GN11-EIP(T+E)]  [Port2 Module Parameter
(EtherNet/IP)]  [Basic Settings]
3.
Click the [Apply] button.
4.
Set the EtherNet/IP communication parameters in "EtherNet/IP Configuration".
[Navigation window]  [Parameter]  [Module Information]  [RJ71GN11-EIP(T+E)]  [Port2 Module Extended
Parameter]
5.
Double-click "<Detailed Setting>" in the "Connection Setting" column and set the connection of the originator.
6.
Select "Tag" in "Connection List" and click the [Add Connection] button.
7.
Select "Connection (Class3/UCMM Tag)" in "Select Connection to be Added:" and click the [OK] button.
13 PROGRAMMING
322
13.4 UCMM Tag Communications Communication Example