8.2
EtherNet/IP Parameter Settings
This section describes the parameter settings required for communications with EtherNet/IP devices.
Procedure for setting parameters
1.
Add the CC-Link IE TSN Plus module (RJ71GN11-EIP) to the engineering tool.
[Navigation window] [Parameter] [Module Information] Right-click [Add New Module]
2.
The basic setting and application setting are included in the parameter settings. Select one of the settings from the tree
on the window shown below.
[Navigation window] [Parameter] [Module Information] Target module [Port2 Module Parameter (EtherNet/IP)]
3.
After setting the parameters, click the [Apply] button.
4.
Set the EtherNet/IP communication parameters in "EtherNet/IP Configuration".
[Navigation window] [Parameter] [Module Information] Target module [Port2 Module Extended Parameter]
5.
Write parameters to the CPU module using the engineering tool.
[Online] [Write to PLC]
6.
The parameters are reflected by resetting the CPU module or powering off and on the system.
Please download the EtherNet/IP configuration tool from Mitsubishi Electric FA Global Site.
8 PARAMETER SETTINGS
112
8.2 EtherNet/IP Parameter Settings