Mitsubishi Electric MELSEC iQ-R Series User Manual page 430

Master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error
Error definition and causes
code
D61BH
Parameter error (device overlap error
(RWw))
D61CH
Parameter error (device overlap error
(RWr))
D61DH
Parameter error (device overlap error
(RY))
D61EH
Parameter error (device overlap error
(RX))
D61FH
Parameter setting by the CCPASET/
CCPASETR instruction has failed.
D621H
Parameter error
D622H
Parameter error (error in the total number
of slave stations)
D625H
Parameter error (station-based block data
assurance setting error)
D628H
Parameter error (station type error)
D629H
Parameter error (station number range
error)
D62AH
Parameter error (data link faulty station
setting error)
D62BH
Parameter error (output setting error
during CPU STOP)
19 LIST OF ERROR CODES
428
19.1 Error Codes When a Module Error Occurs
Action
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the offset or size of the link
device of the slave station in the setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the offset or size of the link
device of the slave station in the setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the offset or size of the link
device of the slave station in the setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the offset or size of the link
device of the slave station in the setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the CCPASET/CCPASETR instruction again after setting "Setting
Method of Basic/Application Settings" under "Parameter Setting Method"
in "Required Settings" to "Program".
• In a redundant system, execute the CCPASETR instruction instead of the
CCPASET instruction.
• Write the network parameter to the CPU module again.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the total number of slave
stations.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the station-based block data
assurance setting.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the station type in the setting
data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the station number in the
setting data so it is within 1 to 120.
• If the error occurs during a firmware update, place the modules according
to the configuration displayed in the "Update Firmware" window, write to
the CPU module, and then update again.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the data link faulty station
setting.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the output settings during
CPU STOP.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
Detailed
information 1
Detailed
information 2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-r cc-link ie tsn plus

Table of Contents