Precautions
■Conditions
• The remote device test does not start even if the 'Remote device forced output request' (SB0016) is turned off and on while
the CPU module is in RUN or PAUSE state.
• Even if the CPU module is changed to STOP state after the 'Remote device forced output request' (SB0016) is turned off
and on, the remote device test does not start.
• If the CPU module is changed to RUN or PAUSE state during the remote device test, the remote device test ends.
■Output HOLD/CLEAR setting function
• During the remote device test, the output HOLD/CLEAR setting function of the remote station is disabled, and the output of
the remote station is turned on or off by the master station. The output HOLD/CLEAR setting function is also disabled for all
remote stations including the remote station whose output is to be turned on or off.
• If a stop error occurs in the CPU module during the remote device test, the test ends and the data is output from the remote
station according to the output HOLD/CLEAR setting function.