Appendix 5 List of Link Special Register (SW)
Description
Stores the information about operating status of the CC-Link IE TSN Network
synchronous communication function for each station.
0: Asynchronous setting
1: Synchronous setting
Stations which are not executing an inter-module synchronous interrupt program
because the CPU operating status is currently STOP or PAUSE (the status under
which the program cannot be executed) are also treated as asynchronous setting (0).
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
SW01C8
16 15 14 13 12 11 10
SW01C9
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
SW01CA
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
SW01CB
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
SW01CC
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
SW01CD
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
SW01CE
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
SW01CF
Each number in the table represents a station number.
 is fixed to 0.
(Conditions)
• Stations that surpass the maximum station number are ignored.
Stores the watchdog counter operating status information for each station in CC-Link
IE TSN network communications.
0: Not operating
1: Operating
Stations that are not performing data links are treated as "0: Not operating" because
the information indicates that the slave station in communication is equipped with a
watchdog counter.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
SW01D0
16 15 14 13 12 11 10
SW01D1
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
SW01D2
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
SW01D3
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
SW01D4
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
SW01D5
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
SW01D6
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
SW01D7
Each number in the table represents a station number.
 is fixed to 0.
(Conditions)
• Stations that surpass the maximum station number are ignored.
Indicates the number of times cyclic data transfer processing is not completed within
the inter-module synchronization cycle. The status is cleared by powering off and on
the system or by resetting the CPU module.
0: Cycle over not occurred
1 to 65535: Cumulative number of times
When FFFFH (maximum value 65535) is counted, counting stops.
Stores the cycle setting value of the fixed interval synchronization of Inter-module
synchronization. (Unit: s)
0 is stored when the inter-module synchronization function is not used.
Stores the request result of 'Remote device forced output request' (SB0016).
0: Normal
1 or greater: Not completed
If not completed, an error code is stored.
When 'Remote device forced output request' (SB0016) is turned off, the stored error
code is cleared.
9
8
7
6
5
4
3
2
120 119 118 117 116 115 114 113
9
8
7
6
5
4
3
2
120 119 118 117 116 115 114 113
Availability
Master
Local station
station
Unicast
mode
1
1
Multicast
mode

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-r cc-link ie tsn plus

Table of Contents