19.3

Error Codes When a Connection Error Occurs

The error code when a connection error occurs during EtherNet/IP communications is stored in 'Class1 connection error
status' (Un\G7734528 to Un\G7735551).
The following shows how error codes are stored.
*1
Address
Un\G7734528
Un\G7734529
Un\G7734530
Un\G7734531
Un\G7734532
Un\G7734533
Un\G7735036
Un\G7735037
Un\G7735038
Un\G7735039
Un\G7735040
Un\G7735041
Un\G7735042
Un\G7735043
Un\G7735044
Un\G7735045
Un\G7735548
Un\G7735549
Un\G7735550
Un\G7735551
*1 An error code is stored in 32 bits.
*2 When StatusIn is 41H or 51H, General Status Code received from the external device is stored.
*3 When StatusIn is 41H or 51H, Extended Status Code received from the external device is stored.
Stored
Stored
Stored
value in (1)
value in (3)
value in (4)
or (2)
or (5)
or (6)
40H (scanner)
10H
0000H
40H (scanner)
20H
0284H
40H (scanner)
20H
0000H
41H (scanner)
01H
0100H
51H (adapter)
41H (scanner)
01H
0103H
51H (adapter)
41H (scanner)
01H
0106H
51H (adapter)
41H (scanner)
01H
0107H
51H (adapter)
Connection destination
Storage method
Input
Connection No.1
Connection No.2
When used as
the target
Connection No.3
When used as
the originator
Connection No.255
Connection No.256
Output
Connection No.1
Connection No.2
When used as
the target
Connection No.3
When used as
the originator
Connection No.255
Connection No.256
Classification Error definition and
causes
Connection
The connection has
disabled
been set to be disabled.
Cyclic
Cyclic transmission is
transmission
stopped.
stop
Cyclic
Cyclic transmission is
transmission
stopped.
stop
CIP Extended
An error notification has
error
been received from the
external device.
CIP Extended
An error notification has
error
been received from the
external device.
CIP Extended
An error notification has
error
been received from the
external device.
CIP Extended
The external device
error
cannot find the
connection to close.
8 bits
8 bits
*2
(1) StatusIn
(3) CIP Status
*2
(1) StatusIn
(5) CIP Status
8 bits
8 bits
(2) StatusOut
(3) CIP Status
(2) StatusOut
(5) CIP Status
Action
• Check the parameter set in "EtherNet/IP Configuration"
and write the parameter to the module again.
• If the same error code is displayed again, the possible
cause is a hardware failure of the error module. Please
consult your local Mitsubishi representative.
• Check whether the operating status of the external device
is normal.
• Check for errors in the line status.
• The line may be busy, so retry the operation after a while.
• Check that a value other than 0 (start request) is set for
'EtherNet/IP communication start request' (Un\G7340096).
• Check that 'Class1 cyclic pause specification'
(Un\G7735808 to Un\G7735823) is set to 0 (no cyclic
pause request).
• Refer to the manuals for the external device and the
EtherNet/IP specification (THE CIP NETWORKS
LIBRARY Volume 1 Common Industrial Protocol (CIP
to check the conditions under which a notification is made
for this error and the action to take.
• Close the connection of the external device and retry.
• Retry after the connection of the external device has been
timed out.
Refer to the manuals for the external device and the
EtherNet/IP specification (THE CIP NETWORKS LIBRARY
Volume 1 Common Industrial Protocol (CIP
conditions under which a notification is made for this error
and the action to take.
Refer to the manuals for the external device and the
EtherNet/IP specification (THE CIP NETWORKS LIBRARY
Volume 1 Common Industrial Protocol (CIP
conditions under which a notification is made for this error
and the action to take.
Check the following items, and then restart the EtherNet/IP
communications.
• Is the operating status of the external device normal?
• Is the line status normal?
19 LIST OF ERROR CODES
19.3 Error Codes When a Connection Error Occurs
16 bits
19
*3
(4) CIP Extended
*3
(6) CIP Extended
16 bits
(4) CIP Extended
(6) CIP Extended
))
)) to check the
)) to check the
435