Communication Test

This function checks if transient transmission data can be properly routed from the own station to the communication target.
Depending on selection for "Communication Method" ("Network No./Station No." or "IP Address"), the range that can be
checked may vary.
Selection of "Communication
Method"
Network No./Station No.
IP Address
The following system configuration is used to explain the procedure of the communication test.
CC-Link IE TSN
Own station
(request source)
Station
Station
No.2
No.0
Network No.1
Station
Station
No.1
No.3
17 CHECKING THE NETWORK STATUS
382
17.1 Checking the Status of CC-Link IE TSN
Communication target of transient transmission
Stations on the same network
 Available for check
 Available for check
Station
No.0
(Relay
(Relay
station 1)
station 2)
Station
Station
Station
No.0
No.2
No.3
Network No.2
Station
No.1
CC-Link IE
Field Network
Station
No.2
Network No.3
Station
No.4
Communication
target
1.
Display the "Communication Test" window and select
"Network No./Station No." or "IP Address" from
"Communication Method".
[Diagnostics]  [CC-Link IE TSN/CC-Link IE Field
Diagnostics]  [Communication Test] button
2.
Enter values for "Target Station" and "Communication
Data Setting".
3.
Click the [Execute Test] button to execute the
communication test. If an error occurs, take corrective
actions according to the error message.
Stations on the other network
 Available for check (relay stations to be transmitted
through can also be checked)
 Not available for check