Mitsubishi Electric MELSEC iQ-R Series User Manual page 427

Master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error
Error definition and causes
code
D268H
The link device range assignment
specified for each station in the CCPASET/
CCPASETR instruction is incorrect.
D269H
The station type of the REMFR/REMTO/
REMFRD/REMTOD/REMFRIP/
REMFRDIP/REMTOIP/REMTODIP
instruction target station is not a remote
station.
D26AH
The target station of the REMFR/REMTO/
REMFRD/REMTOD/REMFRIP/
REMFRDIP/REMTOIP/REMTODIP
instruction does not exist.
D26BH
The network number setting of the
CCPASET/CCPASETR instruction
executing station is incorrect.
D26CH
The station type and station number of the
CCPASET/CCPASETR instruction
executing station are incorrect.
D273H
The request data size of transient
transmission is incorrect.
D275H
Other dedicated instructions are in
execution, and the executed instruction
cannot be processed.
D27CH
The network topology setting of the
CCPASET/CCPASETR instruction is
incorrect.
D2C0H
The network number setting of the
CCPASETX instruction executing station is
incorrect.
D2C1H
The station type and station number of the
CCPASETX instruction executing station
are incorrect.
D2C5H
The IP address of the CCPASETX
instruction is incorrect.
D2C6H
The slave station communication cycle
setting of the CCPASETX instruction is
incorrect.
D2C7H
The number of occupied stations specified
in the CCPASETX instruction is incorrect.
D2C8H
The station type of the CCPASETX
instruction is incorrect.
D2C9H
The station number setting of the
CCPASETX instruction is incorrect.
Action
• Execute the instruction again after correcting the offset or the number of
points of link devices in the network configuration setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Set the station type of the REMFR/REMTO/REMFRD/REMTOD/
REMFRIP/REMFRDIP/REMTOIP/REMTODIP instruction target station to
a remote station.
• Correct the network number and station number/IP address of the target
station of the dedicated instruction.
If the target station of the REMFR/REMTO/REMFRD/REMTOD/REMFRIP/
REMFRDIP/REMTOIP/REMTODIP instruction is disconnected, execute the
dedicated instruction again after return of the target station.
Set "Network No." under "Network No." of "Required Settings" to between 1
and 239.
Rewrite the module parameter using the engineering tool. If the same error
occurs again even after taking the above, the possible cause is a hardware
failure of the error module. Please consult your local Mitsubishi
representative.
• Execute the instruction again after correcting the request command at the
transient request source.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after a while.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the network topology setting
in the control data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
Set "Network No." under "Network No." of "Required Settings" to between 1
and 239.
Rewrite the module parameter using the engineering tool. If the same error
occurs again even after taking the above, the possible cause is a hardware
failure of the error module. Please consult your local Mitsubishi
representative.
• Execute the instruction again after correcting the IP address of the slave
station in the network configuration setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the communication cycle
setting of the slave station in the network configuration setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the number of occupied
stations in the network configuration setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the station type in the
network configuration setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• When "Station Type" in the network configuration setting data is set to
"Master Station", correct "Station Number" to 0 and when "Station Type" is
set to the type other than "Master Station", correct "Station Number" to a
value within 1 to 120. Then, execute the instruction again.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
19 LIST OF ERROR CODES