Mitsubishi Electric MELSEC iQ-R Series User Manual page 428

Master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error
Error definition and causes
code
D2CAH
The total number of slave stations
specified in the CCPASETX instruction is
incorrect.
D2CBH
The network topology setting of the
CCPASETX instruction is incorrect.
D2CCH
The disconnection detection setting of the
CCPASETX instruction is incorrect.
D2CDH
The communication mode of the
CCPASETX instruction is incorrect.
D2CEH
The communication cycle setting of the
CCPASETX instruction is incorrect.
D2D0H
The station number specified for the
CCPASETX instruction is already in use.
D2D1H
The link device range assignment
specified for each station in the
CCPASETX instruction is incorrect.
D2D2H
The IP address/port number of the target
station is incorrect.
D2D3H
Send processing of the transient
transmission has failed.
D602H
Parameter error
D605H
Parameter error
D60BH
Parameter error (device overlap error (LB))
D60CH
Parameter error (device overlap error
(LW))
D60DH
Parameter error (each station device range
assignment error (LB))
19 LIST OF ERROR CODES
426
19.1 Error Codes When a Module Error Occurs
Action
• Execute the instruction again after correcting the total number of slave
stations in the control data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the network topology setting
in the control data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the disconnection detection
setting in the control data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the communication mode in
the control data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting "Setting in Units of 1s",
"Communication Period interval setting", "System Reservation time",
"Cyclic Transmission time", "Normal-Speed", and "Low-Speed" in the
communication cycle setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the station number in the
network configuration setting data to a unique value.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the offset or the number of
points of link devices in the network configuration setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute again after correcting the port number of the target station in the
setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Check the network status using the CC-Link IE TSN/CC-Link IE Field
diagnostics of the engineering tool, and take action.
• When the own station, target station, or relay station detected an error,
identify the cause of the error and take action.
• Execute the instruction again after correcting the target IP address of
transient data.
• If the access destination is a module with a different network number,
correct the routing parameter setting.
• Write the network parameter to the CPU module again.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the offset or size of the link
device of the slave station in the setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the offset or size of the link
device of the slave station in the setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the size of the link device of
the slave station in the setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
Detailed
information 1
Detailed
information 2