Mitsubishi Electric MELSEC iQ-R Series User Manual page 79

Master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Refresh Setting
Assign link refresh ranges between the devices described below.
• SB, SW of the CC-Link IE TSN Plus module  Module label of the CPU module
• SB, SW, link devices (RX, RY, RWr, RWw, LB, LW) of the CC-Link IE TSN Plus module  Devices of the CPU module
■Setting method
The procedure for the refresh settings is shown below.
1.
Set the required items.
2.
Click the [Apply] button to finish the refresh settings.
■Setting items
Item
Description
Device Assignment
Right-click in the setting window and select a link device assignment
Method
method from the "Device Assignment Method" menu.
• Start/End: Enter the start and end numbers of link devices.
• Points/Start: Enter the numbers of points and start numbers of link
devices.
Link Side
Set the link refresh ranges of the link special relay (SB) and link special
register (SW). One range can be set for each SB and SW. ( Page
153 Link refresh)
Ex.
00000H
001FFH
00000H
001FFH
CPU Side
CC-Link IE TSN
Plus module
(1) Module label
(1)
SB
00000H
SW
SW
001FFH
RCPU
Setting range
• Start/End
• Points/Start
(Default: Start/End)
■Device Name
• SB (fixed)
• SW (fixed)
■Points
• SB: 16 to 4096
• SW: 1 to 4096
(Default: 4096)
■Start
• SB: 0H to FF0H (set in increments of 16 points)
• SW: 0H to FFFH (set in increments of 1 point)
(Default: 00000H)
■End
• SB: FH to FFFH (set in increments of 16 points)
• SW: 0H to FFFH (set in increments of 1 point)
(Default: 00FFFH)
■Target
• Module Label
• Specify Device
(Default: Module Label)
■Device Name
• Module Label: 
• Specify Device (link side is SB): SB, M, L, B, D, R, ZR,
RD
• Specify Device (link side is SW): SW, M, L, B, D, R, ZR,
RD
(Default: Grayout)
■Points, End
• Module Label: 
• Specify Device: Displayed according to setting of
"Start".
(Default: Grayout)
■Start
• Module Label: 
• Specify Device: Device range of CPU modules (Set bit
devices in increments of 16 points and word devices in
increments of 4 points.)
(Default: Grayout)
8.1 Parameter Settings for CC-Link IE TSN
8 PARAMETER SETTINGS
8
77