Mitsubishi Electric MELSEC iQ-R Series User Manual page 413

Master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error
Error definition and causes
code
3013H
The value set in "Transient Transmission
Time" in "Communication Period Setting"
under "Basic Settings" of the master
station is smaller than the transient
transmission time calculated using the
number of slave stations and the points of
slave stations set in "Network
Configuration Settings" under "Basic
Settings".
3014H
When "Communication Mode" under
"Application Settings" of the master station
is set to "Multicast", in the "Network
Configuration Settings" of the "Basic
Settings", "Communication Period Setting"
of the local station is set to "Normal-
Speed" or "Low-Speed".
3015H
Any of the items in the module which is set
as a synchronization target in "Inter-
module Synchronization Setting" in
"System Parameter" are set as follows.
• For a local station in which "Network
Synchronous Communication" in
"Network Configuration Settings" of
"Basic Settings" is set to "Synchronous",
"Communication Period Setting" is set to
the setting other than "Basic Period".
• For "Inter-module Synchronization
Setting" in "System Parameter", a
master/local module mounted to an
extension base unit is set as a
synchronization target module.
3016H
When "Network Topology" of "Basic
Settings" of the master station is set to
"Ring", for "Connection Device
Information" under "Basic Settings", set
"CC-Link IE TSN Class Setting" to "Mixture
of CC-Link IE TSN Class B/A or CC-Link
IE TSN Class A Only".
3017H
"0.05ms Unit Setting" of "Fixed Scan
Interval Setting of Inter-module
Synchronization" under "Inter-module
Synchronization Setting" in "System
Parameter" is set to "Not Set".
Action
Set "Communication Period Interval Setting" and "Cyclic Transmission
Time" so that the value of "Transient Transmission Time" in "Communication
Period Setting" under "Basic Settings" of the master station is equal to or
larger than the value shown in the detailed information of module
diagnostics.
• Set "Communication Mode" in "Application Settings" of the master station
to "Unicast".
• In "Network Configuration Settings" under "Basic Settings" of the master
station, set "Communication Period Setting" of the local station to "Basic
Period".
Correct the parameters shown in cause.
• Set "Network Topology" of "Basic Settings" of the master station to "Line/
Star".
• For "Connection Device Information" under "Basic Settings" of the master
station, set "CC-Link IE TSN Class Setting" to "CC-Link IE TSN Class B
Only".
Set "0.05ms Unit Setting" of "Fixed Scan Interval Setting of Inter-module
Synchronization" under "Inter-module Synchronization Setting" in "System
Parameter" to "Set".
19 LIST OF ERROR CODES
19.1 Error Codes When a Module Error Occurs
Detailed
information 1
Detailed
information 2
■
■Communication
Period Interval
Information
• Transient
Transmission Time
19
(Calculation value:
s)
■Parameter
information
• Parameter type
• I/O No.
• Parameter No.
■Target station
information
• Station Number
• IP address
■Parameter
information
• Parameter type
• I/O No.
• Parameter No.
■
■Parameter
information
• Parameter type
• I/O No.
• Parameter No.
■
■Parameter
information
• Parameter type
• I/O No.
• Parameter No.
■
411