Mitsubishi Electric MELSEC iQ-R Series User Manual page 410

Master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error
Error definition and causes
code
2220H
The parameter setting is corrupted.
2221H
• The set value is out of the range. Or the
setting values of the master station and
local stations are not consistent.
• When executing the CCPASETX
instruction, CCPASET instruction, or
M_RJ71GN11_SetParameterX, the
settings of the master station and slave
stations in the network configuration
setting data are not consistent.
• Parameters that are not supported by
the firmware version of the network
module have been set.
• The engineering tool does not support
the parameters that are required to
execute the set functions.
24C0H
An error was detected on the system bus.
24C1H
An error was detected on the system bus.
24C2H
An error was detected on the system bus.
24C3H
An error was detected on the system bus.
24C6H
An error was detected on the system bus.
19 LIST OF ERROR CODES
408
19.1 Error Codes When a Module Error Occurs
Action
Check the detailed information of the error by executing module diagnostics
using the engineering tool, and write the displayed parameter. If the same
error occurs again, the possible cause is a hardware failure of the module.
Please consult your local Mitsubishi representative.
• Check the detailed information of the error by executing module
diagnostics using the engineering tool, and correct the parameter setting
corresponding to the displayed parameter number.
• After reviewing whether the settings of the master station and slave
stations are consistent in the network configuration setting data, execute
the CCPASETX instruction, CCPASET instruction, or
M_RJ71GN11_SetParameterX again.
• Check the firmware version of the network module. If parameters that are
not supported are set, update the firmware version or correct the
parameters.
• Update the version of the engineering tool, and then retry the operation.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of
the module, base unit, or extension cable. Please consult your local
Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of
the module, base unit, or extension cable. Please consult your local
Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of
the module, base unit, or extension cable. Please consult your local
Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of
the module, base unit, or extension cable. Please consult your local
Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of
the module, base unit, or extension cable. Please consult your local
Mitsubishi representative.
Detailed
information 1
Detailed
information 2
■Parameter
information
• Parameter type
■
■Parameter
information
• Parameter type
• I/O No.
• Parameter No.
• Network No.
• Station No.
■
■System
configuration
information
• I/O No.
• Base No.
• Slot No.
• CPU No.
■
■System
configuration
information
• I/O No.
• Base No.
• Slot No.
• CPU No.
■
■System
configuration
information
• I/O No.
• Base No.
• Slot No.
• CPU No.
■
■System
configuration
information
• I/O No.
• Base No.
• Slot No.
• CPU No.
■