No.
Name
Description
SW0045
Module type
Stores the hardware status of the own station.
SW0045 0
Model type
00: Module
01: Board
10: HMI (Human Machine Interface)
SW0046
IPv4 address
Indicates the IP address (IPv4) set in the own station.
to
SW0046
SW0047
SW0047
(1): Third octet
(2): Fourth octet
(3): First octet
(4): Second octet
SW0049
Cause of data
Stores the cause which stopped the data link of the own station.
link stop
00H: At normal communication or power-on
02H: Monitoring time timeout
05H: No slave station (master station only)
10H: Parameter not received (local station only)
11H: Outside the range of own station numbers
12H: Reserved station setting of own station (local station only)
14H: Master station duplication (master station only)
16H: Station number not set (local station only)
18H: Parameter error
19H: Parameter communication in progress
20H: CPU module moderate error, major error
60H: Illegal ring connection (master station only)
(Also used in the CLPA conformance test.)
(Updated even if set as an error invalid station.)
(Updated even if set as a reserved station.)
SW004B
CPU status of
Stores the status of the CPU module on the own station.
own station
00H: No CPU module mounted
01H: STOP (normal)
02H: STOP (moderate/major error)
03H: STOP (minor error)
04H: RUN (normal)
05H: RUN (minor error)
07H: PAUSE
0EH: Reset in progress
0FH: Initial processing in progress
SW004C
Parameter
Stores the status of parameter settings.
setting status
0: Normal
1 or greater: Error definition (Error code is stored.)
(Conditions)
• This register is enabled when 'Received parameter error' (SB004D) is on.
SW0058
Total number of
Stores the total number of slave stations that are set by the parameters.
slave stations
Range: 1 to 120
setting value
SW0059
Total number of
Stores the total number of slave stations that are actually connected by data link.
slave stations
Range: 1 to 120 (0 when own station is disconnected)
present value
Since a local station cannot obtain the station information of the CC-Link IE TSN
Class A remote station when communicating in multicast mode, the CC-Link IE TSN
Class A remote station is reflected as a station where the data link is normally
performed.
b15
b2 b1 b0
0
(1)
(2)
(3)
(4)
Availability
Master
Local station
station
Unicast
mode
Appendix 5 List of Link Special Register (SW)
Multicast
mode
A
*1
APPX
513