Mitsubishi Electric MELSEC iQ-R Series User Manual page 77

Master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Network No.
Set the network number of the own station of the CC-Link IE TSN Plus module.
Item
Description
Network No.
Set the network number of the CC-Link IE TSN Plus module.
Precautions
Set a network number that does not overlap any other network numbers.
In particular, when using an Ethernet-equipped module (CPU module) at default, the IP address is 192.168.3.39 and the
network number is the third octet of the IP address, thus 3. Because setting the network number of the CC-Link IE TSN Plus
module to 3 causes an overlap, set another network number.
Parameter Setting Method
Set the setting method of "Basic Settings" and "Application Settings".
Item
Description
Setting Method of Basic/
Set the setting method of "Basic Settings" and "Application Settings".
Application Settings
Station No./IP Address Setting
Set the items such as the station number and IP address of the own station of the CC-Link IE TSN Plus module.
Item
Description
Station No./IP Address
Select the setting methods of the station number and IP address.
Setting Method
Station No.
Set the station number of the CC-Link IE TSN Plus module. This item can be set only for a local
station.
Set a station number different from those used in the same network.
IP Address
Set the IP address of the own station.
Set an IP address different from those used in other stations. ( Page 198 IP address
duplication detection)
Do not set the following values.
• The third and fourth octets are all 0 or all 1.
• The host address bits are all 0 or all 1
• Reserved address
Subnet Mask
Set the subnet mask.
Set the same value for the master station and slave station.
If the subnet mask is empty, the address class (class A, class B, class C) is determined from the
setting of "IP Address", and operation is done with the subnet mask according to the address
class.
The subnet mask for each class is as follows.
• Class A: 255.0.0.0
• Class B: 255.255.0.0
• Class C: 255.255.255.0
The IP address for each class is as follows.
• Class A: 0.x.x.x to 127.x.x.x
• Class B: 128.x.x.x to 191.x.x.x
• Class C: 192.x.x.x to 223.x.x.x
The host address for each class is the 0 section shown below.
• Class A: 255.0.0.0
• Class B: 255.255.0.0
• Class C: 255.255.255.0
Default Gateway
Set the default gateway.
Precautions
The IP address to be set should have a different segment from the IP address to be set on the EtherNet/IP side. ( Page
113 Own Node Settings)
Setting range
1 to 239
(Default: 1)
Setting range
Parameter Editor (fixed)
Setting range
Parameter Editor (fixed)
• Master station: Fixed to "0"
• Local station: 1 to 120
(Default: 1)
0.0.0.1 to 223.255.255.254
(Default: Master station
192.168.3.253, other than the
master station 192.168.3.1)
• Empty
• 0.0.0.1 to 255.255.255.255
(Default: empty)
• Empty
• 0.0.0.1 to 223.255.255.254
(Default: empty)
8 PARAMETER SETTINGS
8.1 Parameter Settings for CC-Link IE TSN
8
75

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-r cc-link ie tsn plus