Connection Device Information
Set the information of the connected device.
Item
Description
CC-Link IE
Sets the CC-Link IE TSN Class of connected devices.
TSN Class
Setting
TSN HUB
Sets whether to use a TSN hub when a CC-Link IE TSN Class B device and CC-Link IE
Setting
TSN A device coexist.
When connecting a TSN hub, set "Use TSN HUB".
Precautions
To connect a TSN hub when a CC-Link IE TSN Class B device and CC-Link IE TSN Class A device coexist, set "TSN HUB
Setting" to "Use TSN HUB".
Slave Station Setting
Set items related to the slave station.
Item
Description
Disconnection
Set the number of consecutive communication failures until a slave station is considered disconnected.
Detection
Setting
Own Node Settings
Set items related to the own node.
Item
Description
Opening
Select how to open a connection when using UDP/IP communications or Passive open of TCP/IP
Method
communications.
• When "Do Not Open by Program" is selected, a connection is open when the system receives the Active
request. Program for open/close processing is not required.
• When "Open by Program" is selected, the open/close processing is performed by a program. The
module cannot communicate when the CPU module is in STOP state.
Setting range
• CC-Link IE TSN Class B Only
• Mixture of CC-Link IE TSN Class B/A or CC-
Link IE TSN Class A Only
(Default: CC-Link IE TSN Class B Only)
• Not to Use TSN HUB
• Use TSN HUB
(Default: Not to Use TSN HUB)
Setting range
• 2 times
• 4 times
• 8 times
(Default: 4 times)
Setting range
• Do Not Open by Program
• Open by Program
(Default: Do Not Open by
Program)
8 PARAMETER SETTINGS