■Multicast mode
• The master station and local station send data on the line in multicast mode in each send range.
• The CC-Link IE TSN Class A local station communicates data in the same communication range as the CC-Link IE TSN
Class B local station.
RCPU
X
0000H
001FH
0020H
003FH
Y
0000H
001FH
0020H
003FH
W
0000H
000FH
0010H
001FH
0000H
000FH
0010H
001FH
No.0, No.1, No.2: Station No.0 (master station), station No.1, station No.2
No.1, No.2: Send range: to station No.1, send range: to station No.2
No.1, No.2: Send range: from station No.1, send range: from station No.2
• Output from the master station
 The device is turned on by the sequence scan of the CPU module in the master station, and END processing is performed.
 The device status of the CPU module is stored in the link devices (RY, RWw) of the master station by link refresh.
 The status of the link devices (RY, RWw) of the master station is stored in the link devices (RX, RWr) of the local station on the same network by cyclic data
transfer processing.
 The status of the link devices (RX, RWr) of the local station is stored in the devices of the CPU module by link refresh.
• Input from the local station
 The device is turned on by the sequence scan of the CPU module in the local station, and END processing is performed.
 The device status of the CPU module is stored in the link devices (RY, RWw) of the local station by link refresh.
 The status of the link devices (RY, RWw) of the local station (station No.2) is stored in the link devices (RX, RWr) of the master station on the same network
and the link devices (RY, RWw) of the local station (station No.1) by cyclic data transfer processing.
 The status of the link devices (RX, RWr) of the master station is stored in the devices of the CPU module by link refresh.
TSN HUB
No.0
RX
0000H
No.1
001FH
0020H
No.2
003FH
RY
0000H
No.1
001FH
0020H
No.2
003FH
RWr
0000H
No.1
000FH
0010H
No.2
001FH
RWw
0000H
No.1
000FH
0010H
No.2
001FH
No.1
No.2
RX
RX
0000H
No.1
No.1
001FH
0020H
No.2
No.2
003FH
RY
RY
0000H
No.1
No.1
001FH
0020H
No.2
No.2
003FH
RWr
RWr
0000H
No.1
No.1
000FH
0010H
No.2
No.2
001FH
RWw
RWw
0000H
No.1
No.1
000FH
0010H
No.2
No.2
001FH
RCPU
X
Y
W
9 FUNCTIONS
145
9.2 Cyclic Transmission